Egate-100 Ver. 4.0 Site Requirements and Prerequisites 2-1
Chapter 2
Installation and Setup
This chapter describes installation and setup procedures for the Egate-100 unit.
After installing the unit, refer to
Chapter 3
for operating instructions.
If a problem is encountered, refer to
Chapter 5
for test and diagnostic
instructions.
Egate-100 ships completely assembled. It is designed for installation as a desktop
unit or mounted in a 19-inch rack. For rack installation instructions, refer to the
documentation that comes with the RM kit.
Internal settings, adjustment, maintenance, or repairs must be performed only by
a skilled technician who is aware of the hazards involved.
Always observe standard safety precautions during installation, operation, and
maintenance of this product.
For your protection and to prevent possible damage if a fault condition such as a
lightning strike or contact with high voltage power lines occurs on the cables
connected to the equipment, Egate-100 must be properly grounded at all times.
Any interruption of the protective (grounding) connection inside or outside the
equipment, or disconnection of the protective ground terminal, can make this
equipment dangerous. Intentional interruption is prohibited.
2.1 Site Requirements and Prerequisites
AC-powered Egate-100 units should be installed within 1.5 meters (5 feet) of an
easily accessible and grounded AC outlet, capable of furnishing the required
supply voltage in the range of 100 to 240 VAC, at 50/60 Hz.
DC-powered Egate-100 units should be connected to -48 or -60 VDC mains in
accordance with the
DC Connection Supplement
.
Allow at least 90 cm (36 in) of frontal clearance for operator access. For
continuous product operation allow at least 10 cm of frontal clearance, and at
least 15 cm at rear of the unit, for cable connections and ventilation. For proper
ventilation, keep at least 2.5 cm clearance from the sides and top of the product.
The ambient operating temperature of Egate-100 is 0°
to 50° C (32° to 122°F), at
a relative humidity of up to 90%, non-condensing.
See also the sections describing connections of AC and DC mains at the beginning
of this manual.
Warning
Warning
Note