118 Rockwell Automation Publication 750-TD001H-EN-P - June 2013
PowerFlex 750-Series AC Drives
PowerFlex 755 System Resource Allocation
Some drive configurations utilizing certain communication options may exceed the available resources of the processor
located on the Main Control Board. This is a consideration for PowerFlex 755 drives with revision 2 (or later) firmware.
Refer to the PowerFlex 750-Series Programming Manual, publication 750-PM001 for details.
PowerFlex 750-Series Legacy Communication Options
Most legacy communication adapters (20-COMM) can be used with the PowerFlex 755. However, the restrictions stated
below do apply.
Frame 1 - It is recommended that the 20-750-20COMM-F1 Communication Carrier Card only be installed in Port 4.
Port 5 will not be accessible when this module is installed.
Frames 2 and larger - It is recommended that the 20-750-20COMM Communication Carrier Card be installed in Port 6.
Using Port 4 or 5 will make the adjacent left port inaccessible to other option modules and may interfere with network
cable connections. For details, contact Allen-Bradley Drives Technical Support.
Environmental Specifications – Communication Modules
Adapter
Accesses Ports 2, 3 and 6
for I/O Connections
(Implicit & Explicit Messaging) Accesses Port 7…14 Devices Supports Drive Add On Profiles Supports Asian-Languages
(6)
(6) Chinese, Japanese, and Korean languages are supported at the time of publication.
20-COMM-B Not Compatible
20-COMM-C
(2)
(2) Controller must be capable of reading/writing 32-bit floating point (REAL) values.
v3.001
(4)
(4) Requires this adapter firmware version or higher.
(5)
(5) Requires firmware version v1.05 or higher of the drive Add On Profiles for RSLogix 5000 version v16 or higher.
v3.001
(4)
20-COMM-D Not Compatible
20-COMM-E v4.001
(4)
(5)
v4.001
(4)
20-COMM-H v2.009
(3)
(3) Supports all three modes of operation (RTU, P1, N2).
Not Compatible20-COMM-K v1.001
(4)
20-COMM-L v1.007
(4)
20-COMM-M
(2)
v2.001
(4)
Not Compatible v2.001
(4)
20-COMM-Q
(2)
v3.001
(4)
(5)
v3.001
(4)
20-COMM-R
(1)
(1) This item has Silver Series status. For information, refer to http://www.ab.com/silver.
Not Compatible
20-COMM-S
Temperature
Operating:
Storage:
-10…50 °C (14…122 °F)
-40…85 °C (-40…185 ° F)
Relative Humidity: 5 to 95% non-condensing
Atmosphere: Important: The module must not be installed in an area where the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the module is not going to be installed for a period of time, it must be stored in an area where it will
not be exposed to a corrosive atmosphere.